如何校准?
总体来说:如果出水偏少,请调大K值;如果出水偏多,请调小K值。
具体的校准过程如下:
输入参考K值(由厂家提供,或者当前使用的K值),实际测量一分钟的过水总量,用量具称量,或者接满一个矿泉水瓶的水,然后与显示数值进行比对。
如果精度不能满足要求,
用以下公式计算出新的K值:
参考K值(当前K值)X 流量显示值 ÷ 实际称量值(矿泉水瓶容积)=校准后的新K值。
输入新K值再次重复上述校准步骤,一般进行2次校准以后就很准确了。
例如,出厂K值,或者当前K值为5,定量10L,出水称重 11L,那么新的K值就是
5*10/11=4.55 4.55就是新的K值
Generally speaking: if the water output is lower than the setting, increase the K value; if the water output is higher, decrease the K value.
The specific calibration process is as follows:
Enter the reference K value (provided by the manufacturer,Or the current K value),
Measure the total amount of water in one minute, weigh it with a measuring tool,
OR
Fill up a mineral water bottle,
then compare it with the displayed value.
If the accuracy cannot meet the requirements,
Use the following formula to calculate the new K value:
Reference K value(OR current K value) X flow display value ÷ actual weighing value (volume of mineral water bottle) = new K value.
Enter the new K value and repeat the above calibration steps again.
Generally, it is very accurate after two times calibrations.
For example, if the factory K value or the current K value is 5, the target amount is 10L, but the actual water output is 11L, then the new K value is calculated as:
New K value=5*10/11≈4.55
Thus, 4.55 is the new K value.